750-306 DeviceNet interface to the Wago-I/O-system
In stock
DeviceNet field-bus coupler; 125 kbit/s to 500 kbit/s; digital and analog signals; carrier rail DIN 35; cage clamp connection
This buscoupler connects the Wago-I/O-System as a slave to the DeviceNet field-bus.
The buscoupler configures automatically, creating a local process image which may include analog, digital or specialty modules. Analog and specialty module data is sent via words and/or bytes, digital data is sent bit by bit.
DeviceNet stores the process image in the corresponding Master control (PLC, PC or NC).
The local process image is divided into two data zones containing the data received and the data to be sent.
The process data can be sent via the DeviceNet field-bus to the PLC, PC or NC for further processing, and received from the field via DeviceNet.
The data of the analog modules is stored in the process image which is created automatically according to the order in which the modules are connected to the buscoupler. The bits of the digital modules are sent byte by byte and added to the analog data. If the amount of digital information exceeds 8 bits, the buscoupler automatically starts with a new byte.




Wago Kontakttechnik