CAN in Automation (CiA)
headquarters@can.cia.org
www.can-cia.org
CANopen Product Guide 2011
home

Telemecanique

www.telemecanique.com

NMT
NMT master
Error control
Node guarding
Heartbeat producer
Heartbeat consumer
Boot-up
Yes
Node ID range
-
Node ID assignment
No
CANopen bit-rates
-
Type of bit-rate adjustment
-
No. of PDO
RPDOs
9
TPDOs
9
PDO modes
Synchronous (cyclic)
Synchronous (acyclic)
PDO linking
No
PDO mapping
Static
Emergency message
-
Producer:
-
Consumer:
No. of SDO
Server
No
Client
64
Sync
No
Sync producer:
No
Sync counter:
Time stamp
No
Additional functions
None
Supported application layer
CiA 301 V 4.0.2
Supported frameworks
None
Supported profiles
CiA 405: CANopen interface and device profile for IEC 61131-3 programmable devices
Certified
No

Headquarters

Schneider Electric Industries SAS
35 rue Joseph Monier
CS 30323
FR-92506 Rueil Malmaison Cedex

URL: www.schneider-electric.com
URL: www.telemecanique.com

Altivar Controller Inside interface board and controller

Availability
In stock

Programmable card for frequency inverters for 3-phase asynchronous motors

Description

The "Controller Inside" programmable card is used to adapt the variable speed drive to specific applications by integrating control system functions.

It can be programmed by PowerSuite 1131 in IEC 1131-3.

It fits into Altivar 61 and 71 variable speed drives.

Various predefined configurable applications are sold by Telemecanique and its partners.

It is not possible to transfer the program from the card to the PC, which enables us to protect the know-how.

Interfaces

  • 10 logic inputs, two of which can be used for two counters or four of which can be used for two incremental encoders
  • 2 analog inputs
  • 6 logic outputs
  • 2 analog outputs
  • A master port for the CANopen network
  • A PC port for programming with the PowerSuite 1131 software workshop

A single "Controller Inside" programmable card can be fitted in the Altivar 71 drive. It can be combined with another option card (I/O extension or communication).

The "Controller Inside" programmable card can also use:

  • The drive I/O
  • The I/O extension card I/O
  • The encoder interface card counter
  • The drive parameters (speed, current, torque, etc)

Supply

If the power consumption does not exceed 200 mA, this card can be powered by the drive. Otherwise, an external 24 VDC power supply must be used.

Programming software

The PowerSuite 1131 software workshop for PC is used for programming and debugging new applications, quickly and in an open-ended manner.

It complies to international standard IEC 61131-3, six programming languages are available:

  • Ladder language (LD)
  • Structured Text language (ST)
  • Grafcet language (SFC)
  • Instruction List language (IL)
  • Function blocks (DFB)
  • Continuous Flow Chart (CFC)

The PowerSuite 1131 software workshop has pre-programmed function blocks (standard library) and offers users the option of creating their own function blocks (user library).

The standard library contains:

  • Logic functions (AND, OR, etc)
  • Mathematical functions (Cos, Sin, Exp, etc)
  • Function blocks dedicated to drives which simplify data exchanges between the drive and the "Controller Inside" programmable card (example: sending the speed reference)
  • Function blocks for managing the CANopen bus
  • Graphic terminal display function blocks

Various functions are used to debug the application program:

  • Display changes in variables (table of variables and oscilloscope)
  • Force variables
  • Place breakpoints
  • Execute the program step by step